10-144A
Chapter 226
STATE OF
CROSS CONNECTION RULES
DEPARTMENT OF HUMAN SERVICES
DIVISION OF HEALTH
ENGINEERING
10 STATE HOUSE STATION
EFFECTIVE DATE
These rules are effective July 10, 2001
7/24/00
10-144A Department of Human
Services
Chapter
226 Bureau of
Health
Drinking Water Program
STATE OF
CROSS CONNECTION RULES
SUMMARY STATEMENT
These rules are designed to
regulate, control, and prevent the contamination of drinking water by the
backflow of water or other liquids, mixtures or substances into the
distribution pipes of a water supply system from a source or sources other than
its intended source.
BASIS STATEMENT
Since it is the
responsibility of a public water supply to provide water, which is safe to
consume, and since active, unprotected, or inadequately protected
cross-connections provide a real and present threat to the safety of the water
being consumed, these rules are promulgated.
AUTHORITY
These rules are authorized
under 22 M.R.S.A. Chapter 601, Subchapter II § 2612(5).
In accordance with Title VI
of the Civil Rights Act of 1964, as amended by
The Civil Rights Restoration
Act of 1991 (42 U.S.C. 1981, 2000e et
seq.)
Section 504 of the
Rehabilitation Act of 1973, as amended (29 U.S.C. 794),
The Age Discrimination Act of 1975,
as amended (42 U.S.C. 6101 et seq.),
Title
II of the Americans with Disabilities Act of 1990 (42 U.S.C. 12101 et
seq.),
and Title IX of the Education Amendments of 1972, the
Department
of Human Services does not discriminate on the basis of sex,
color,
national origin, disability or age in admission or access to or treatment
or
employment in its programs and activities.
i
TABLE OF CONTENTS
Section Page
1.
General Provisions 1
1.1
Application and Scope 1
1.2
Constitutionality 1
2.
Definitions 1
3. Administration 3
4. Cross Connection Control
Programs 3
5. Degree of Hazard 4
5.1 Class I 4
5.2 Class II 4
5.3 Class III 4
6. Approved Anti-backflow
Devices 4
6.1 Class I 4
6.2 Class II 4
6.3 Class III 4
7. Permits 5
8. Exemptions 5
9. Responsibility 6
ii
A.
The provisions of these
rules shall apply to all public water systems, with a population of greater
than 1,000 or with an industrial account.
A.
Should any section,
paragraph, sentence, clause, or phrase of these
Rule be declared
unconstitutional or invalid for any reason, such decision shall not affect the
validity of the remaining portion of these rules.
A. Air-gap Separation – A physical separation
between the free flowing discharge end of a potable water supply pipeline and
an open or non-pressure receiving vessel. An air-gap separation shall be at
least twice the diameter of the supply pipe measured vertically above the
overflow rim of the vessel – in no case less than one inch (2.54 cm).
B. Anti-backflow Device - A device or means to prevent backflow.
C. Approved Source - A source of water utilized by a public water system for distribution to the public for consumptive purposes and which is approved by the Department for such use following a required and/or approved treatment process.
D. Backflow Preventer - An anti-backflow device.
E. Backflow - The undesirable reversal of the flow of water or mixtures of water and other liquids, gases or other substances into the distribution pipes of a potable water supply from any source or sources other than the public water system’s approved source.
F. Backflow Preventer, Reduced Pressure
Principle Type - An assembly of differential valves and check valves including
an automatically opened spillage port to the atmosphere.
G. Back-siphonage - Backflow resulting from
negative pressures in the distribution pipes of a potable water supply.
H. Contaminant – Any chemical, biological, or
radiological substance or matter which is an impairment of the water quality of
the water which creates an actual hazard to the public health through poisoning
or through the spread of disease by sewage, industrial fluids or waste.
I. Cross-connection - Any physical connection,
or structural arrangement between two otherwise separate systems, one of which
contains potable water and the other which contains water of unknown or
questionable safety and/or steam, chemicals, gases or other contaminants and/or
pollutants, whereby there may be a flow of an unapproved water to a potable
water supply.
J. Department - Maine Department of Human Services.
K. Industrial Fluids – Shall mean any fluid or solution which may be chemically, biologically or otherwise contaminated or polluted in a form or concentration such as would constitute a health, system, pollutional or plumbing hazard if introduced into an approved water supply. This may include, but is not limited to: polluted or contaminated used waters; all types of process waters and “used waters” originating from public potable water system which may deteriorate in sanitary quality; chemicals in fluid form; plating acids and alkalies; circulated cooling waters connected to an open cooling tower and/or cooling waters that are chemically or biologically treated or stabilized with toxic substances; contaminated natural waters such as from wells, springs, streams, rivers, bays, harbors, seas, irrigation canals or systems, etc.; oils, gases, glycerine, paraffines, caustic and acid solutions and other liquid and gaseous fluids used in industrial or other processes or for fire fighting purposes.
L. Owner - Any person who has legal title to, or license to operate or inhabit, a property upon which a cross-connection inspection is to be made or upon which a cross-connection is present.
M. Person - Any individual, partnership, company, public or private corporation, political subdivision or agency of the state, Department, agency or instrumentality of the United States or any other legal entity.
N. Political subdivision - Any
municipality, county, district or any portion or combination of 2 two or
more thereof.
O. Pollutant - A foreign substance that impairs the quality of the water to a degree which does not create a hazard to the public health but which does adversely and unreasonably affect the aesthetic quality of such water for domestic use.
P. Potable Water - An approved water source, free from impurities present in any amount sufficient to cause disease or harmful physiological effects. An approved water source physical, bacteriological, chemical and radiological quality must conform with the requirements of the Maine State Rules Relating to Drinking Water.
Q. Public Water System –Is hereby incorporated
by reference as defined in Chapter 22 M.R.S.A. § 2601 and 10-144 CMR 231
Section 2 in the State of
R. Startup Date – The date a
public water system starts providing water to its customers.
S. Supplier - Any person who
controls, owns or generally manages a public water system.
T.
System - Public Water System.
A. The supplier shall not allow a
cross-connection at any point within its system unless approved pursuant to an
application submitted to the Department for the cross-connection.
B. The owner shall be responsible for ensuring
the proper operation and maintenance of an anti-backflow device and the
periodic regular testing of the device.
C. The supplier shall be responsible for the administration of its cross-connection control program and ensuring that the periodic testing of anti-backflow devices are performed.
4. CROSS
CONNECTION CONTROL PROGRAMS
A. All suppliers serving a population of more than one thousand (1,000) people shall submit a written cross-connection control program to the Department within sixty (60) days of the date the system is established or the population served increased. The cross-connection control program shall be implemented and in effect within a period not to exceed nine (9) months after approval by the Department.
B. Any supplier serving a population of less
than one thousand (1,000) people but which has an industrial account
account shall submit a written cross-connection
control program to the Department within sixty days (60) of the date the
industrial account becomes active. The cross-connection control program shall
be implemented and in effect within a period not to exceed nine (9) months
after approval by the Department.
C. All new suppliers required to have a
cross-connection control program shall submit a written cross-connection
control program to the Department for approval, within sixty days (60) of the
startup date. The cross-connection
control program shall be implemented and in effect within a period not to
exceed nine (9) months after approval by the Department.
D. The Department specifically reserves the right to inspect all cross-connections. The supplier shall be administratively responsible for the corrections necessary as a result of a Departmental inspection. The owner and/or supplier shall comply with any Departmental or supplier's orders issued as a result of said inspections of the water system.
A. For the purpose of these rules the following classifications of Degree of Hazard and associated definitions shall apply:
5.1 Class I - Low
degree of hazard
If a backflow were to occur, the resulting health significance would be limited to minor changes in the aesthetic quality such as taste, odor or color. The foreign substance must be non-toxic and non-bacterial in nature with no significant health effect.
5.2 Class II -
Moderate degree of hazard
If a backflow were to occur, the resulting effect on the
water supply would result in significant (detectable) changes in
aesthetic qualities. The foreign
substance (pollutant) must be non-toxic, (non-harmful) to humans.
5.3 Class III -
High degree of hazard
If a backflow were to occur, the resulting effect on the
water supply could cause illness or death if consumed by humans. The foreign
substance (contaminant) may be toxic and/or harmful to humans either
from a chemical, bacteriological or radiological standpoint. The effects of the contaminants may result
from short or long-term exposure.
6. APPROVED
ANTI-BACKFLOW DEVICES
A. Only the following types of anti-backflow
devices may be used in a permitted cross-connection:
Degree of Hazard Allowed
Devices
6.1
Class I Air-Gap
Separation
Atmospheric
Type Vacuum Breaker
Pressure
Type Vacuum Breaker
Double
Check Valve Assembly
Reduced
Pressure Principal Device
6.2
Class II Air-Gap
Separation
Pressure
Type Vacuum Breaker
Double
Check Valve Assembly
Reduced
Pressure Principal Device
6.3 Class III Air-Gap
Separation
Reduced
Pressure Principal Device
A. The supplier shall not allow a cross-connections within the public water supply system unless deemed necessary by the supplier.
B. All cross-connection permits applications shall be
submitted to and reviewed by the Department.
C. Records of cross-connection control devices
shall be kept on file with the supplier for a minimum of five (5) years from
the date of issuance, and shall be available for inspection by Department
staff.
D. It shall be the supplier's responsibility to review the degree of hazard of the cross-connection, assign the proper classification to a specific cross-connection and designate the proper classification on the specific cross-connection permit application.
E. The owner shall apply for a cross-connection
permit on appropriate forms and submit said application in triplicate to the
supplier.
F. The supplier shall forward the permit
application to the Department along with the degree of hazard classification,
in addition to recommendations as to whether or not the permit shall be
issued. Permits shall be renewed every
five (5)
years. Requests for permit renewal shall
be reviewed by the supplier, and if no changes have occurred the permit shall
be automatically renewed. If changes
have occurred during any permit period, the renewal application shall be
reviewed for a modification to the degree of hazard determination.
G. Permits shall be non-transferable.
A. Any existing backflow preventer shall be
allowed to continue in service unless:
1. The supplier and/or Department considers the condition of any portion of the device to be such that replacement should be made, or
2. The degree of hazard is changed.
B. Specific exemptions from these rules are permitted. Specific conditions and devices exempted are found in Appendix A.
C. The Commissioner may grant one or more
exemptions from this rule to a public water system or owner, if
1. The exemption will not result in an
unreasonable risk to the public health; and/or
2. The public water system or owner is unable to comply with the regulation due to compelling factors, not including economic factors.
D. An exemption shall not alter the degree of hazard classification of the cross-connection and shall not exclude the use of some appropriate anti-backflow device not necessarily assigned to the particular degree of hazard assigned to the cross-connection. Prior to granting an exemption, the Commissioner shall provide notice in a local newspaper and give an opportunity for public hearing on the proposed exemption. Each exemption may also be conditioned on monitoring, testing, analyzing or other requirements to ensure the protection of the public health, and shall include a compliance schedule.
A. It shall be the responsibility of the
supplier and owner to ensure that no unprotected cross-connection is present.
If the supplier has reasonably ordered an owner to protect its water supply
from a potential cross-connection and the owner does not do so, the supplier
shall be required to discontinue service to the owner within a period of time
specified in the water supplier's Cross-Connection Control Program. Notice shall
be given to the Department and to the Maine Public Utilities Commission.
C. All owners maintaining cross-connections
between their private system and the supplier's water system shall eliminate
and disconnect such cross-connections unless deemed necessary by the water
supplier and the Department, and protected by a backflow preventer approved by
the Department and permitted for the degree of hazard associated with the
cross-connection. Such disconnection
shall occur within six months of the effective date of the cross-connection
control program.
D. It shall be the responsibility of the owner
to inform the supplier of any new, existing, proposed or modified
cross-connection.
E. It shall be the responsibility of the owner
to provide access during normal working hours to the premises for any
representative of the supplier or to any representative of the Department or
any other state or federal agency authorized to do so for the expressed purpose
of inspecting for possible cross-connections or gaining information in the
preparation of a permit. This shall include providing copies of any plans,
drawings, reports or specifications relating to the water system or proposed
cross-connection control devices.
F. It shall be the responsibility of the owner to comply with all provisions of any permit and the supplier's Cross-Connection Control Program.
EXEMPTED DEVICES AND SITUATIONS
1. Water closets fitted with anti-siphon ball-cocks and installed in accordance with § 1003b of the Maine State Plumbing Code shall be permitted without further protection.
2. Urinal and water closet flushometer valves fitted with approved vacuum breakers and installed in accordance with § 1003(a)(c) of the Maine State Plumbing Code shall be permitted without further protection.
3. Irrigation systems with “Pop-up” sprinklers shall be allowed if protected by a double-check valve assembly with an intermediate atmospheric vent
4. Irrigation systems with heads permanently elevated at least twelve (12) inches above the surrounding ground level elevation shall be protected by a double-check valve assembly with an intermediate atmospheric vent installed.
5. Boilers in non-industrial application and not containing toxic chemicals may be fitted with approved double-check valve assemblies with intermediate atmospheric vents